Nippon ∆T Indicator
∆T controllers are use for COOLING TOWERS. ENERCON2000 is a state of art micro controller based instrument idealy used for energy saving In cooling towers. The cooling tower in is switched ON & OFF as per the logic designed and Incorporated by ENERCON2000. This leads to tremendous saving of electricity bill.
- Specifications
Inputs | 3 channels; T(Inlet), T(Outlet) and T(Ambient) |
---|---|
Sensor | Pt100, 3 wire R.T.D. 's |
Range | 0-60 °c |
Setpoint | 2 set points T(F) and T(Ref) |
Output | 1Relay rated 230 V, 6 Amp. |
Setting | By soft touch membrane key pads |
Supply | 90-260 VAC , 50 Hz |
Box | 96(H) x 192(W) Din size ABS molded box |
Logic | T(Inlet) is Input to cooling tower, T(Outlet) is cold water coming out from cooling to T(Inlet) -T(Outlet) > T(F) fan ON T(Inlet) -T(Outlet) < T(F) fan OFF T(Ambient) > T(Ref) fan ON T(Ambient) < T(Ref) fan OFF |